High-Precision Automatic Portable SF6 Dew Point Analyzer with Chilled Mirror Technology for GIS & SF6 Gas Systems

Miejsce pochodzenia Szanghaj
Nazwa handlowa KSTONE
Orzecznictwo ISO9000
Numer modelu KST-V
Minimalne zamówienie 1
Cena $10000-15000
Szczegóły pakowania Karton/drewniane pudełko
Czas dostawy 15 dni roboczych
Zasady płatności T/T
Możliwość Supply 1000 jednostek rocznie
Szczegóły Produktu
Wyświetlacz °C / ppm Natężenie przepływu gazu 400~800 ±50 ml/min
Wyświetlacz przepływu cyfrowy przepływometer Ciśnienie gazu ≤1 MPa
Temperatura otoczenia -20°C ~ +50°C Wilgotność otoczenia ≤85% RH
Podkreślić

portable SF6 dew point analyzer

,

automatic chilled mirror dew meter

,

GIS SF6 gas dew analyzer

Zostaw wiadomość
opis produktu
High-Precision Automatic SF6 Chilled Mirror Dew Point Analyzer For GIS & SF6 Gas Systems
Product Overview

The KST-V SF6 Chilled Mirror Dew Point Analyzer is a high-precision moisture measurement instrument specially designed for SF6 gas systems, GIS equipment and high-voltage electrical maintenance applications.

The analyzer adopts the chilled mirror measurement principle, providing highly accurate and stable dew point measurement results with excellent long-term reliability. Compared with conventional sensor-type dew point meters, the chilled mirror method offers higher measurement accuracy, superior repeatability and reduced drift over time.

The instrument supports fully automatic continuous measurement and automatic mirror heating/defrosting cycles, ensuring stable operation in field testing environments.

Equipped with a built-in lithium battery, digital flowmeter and intelligent control system, the KST-V is suitable for on-site SF6 gas moisture analysis in substations, GIS switchgear maintenance, gas recovery systems and power utility inspection applications.


How Chilled Mirror Dew Point Analyzer Works
Chilled Mirror Measurement Principle

The analyzer operates based on the chilled mirror dew point measurement principle.

When the gas temperature drops below the saturation temperature of water vapor under a certain pressure condition, moisture in the gas condenses on the mirror surface. The reflected light changes due to diffuse reflection caused by condensation, and the optical sensing system detects this variation.

The intelligent control system analyzes both optical and temperature signals to accurately calculate the dew point temperature of the tested gas.

After dew formation is detected, the instrument automatically heats the mirror surface until condensation disappears, then starts a new cooling cycle for continuous automatic measurement.

Below 0°C, the measured dew point is referred to as the frost point.

Chilled Mirror Dew Point Analyzer working principle diagram
Main Features
  • High-precision chilled mirror measurement technology
  • Specially designed for SF6 gas moisture analysis
  • Fully automatic continuous measurement
  • Automatic mirror heating and defrost cycle
  • High measurement stability with minimal drift
  • Digital flowmeter display
  • Dual display units: °C and ppm
  • Built-in rechargeable lithium battery
  • Portable compact structure for field operation
  • Suitable for GIS and high-voltage electrical maintenance

Applications
  • GIS switchgear moisture testing
  • SF6 gas quality analysis
  • High-voltage substation maintenance
  • SF6 gas recovery and filling systems
  • Electrical power utility inspection
  • Gas insulated equipment commissioning
  • Preventive maintenance of SF6 electrical equipment

Technical Specifications
Item Specification
Measurement Principle Chilled Mirror Method
Measured Gas SF6
Measurement Mode Fully Automatic Continuous Measurement
Dew Point Range +20°C to -62°C
Temperature Resolution 0.1°C
Measurement Accuracy Better than ±0.3°C
Display Unit °C / ppm
Gas Flow Rate 400~800 ±50 ml/min
Flow Display Digital Flowmeter
Gas Pressure ≤1 MPa
Refrigeration Source SL Micro Cooler
Sampling Interface Self-sealing Quick Connector
Ambient Temperature -20°C ~ +50°C
Ambient Humidity ≤85% RH
External Power Supply AC220V ±10%, 50Hz
Internal Power Supply 24V Lithium Battery
Power Consumption ≤70W
Continuous Working Time >8 Hours
Dimensions 340 * 230 * 200 mm
Weight ≤9.5 kg
Standard Configuration
  • KST-V Dew Point Analyzer
  • Power Adapter
  • Sampling Hose
  • Self-sealing Quick Connectors
  • User Manual
  • Carrying Case

Optional Accessories
  • SF6 pressure reducing valve
  • Stainless steel sampling hose
  • Additional quick connectors
  • External gas filter unit
  • Calibration service

Frequently Asked Questions
Why use chilled mirror technology instead of conventional sensor-type dew point meters?

Chilled mirror technology provides direct physical dew point measurement with higher accuracy, better repeatability and long-term stability compared with conventional polymer sensor technology.


Is the analyzer suitable for GIS switchgear maintenance?

Yes. The KST-V is specifically designed for GIS equipment, SF6 gas systems and high-voltage electrical maintenance applications.


Can the instrument display ppm values?

Yes. The analyzer supports both dew point temperature (°C) and ppm moisture content display.


Does the analyzer support field operation?

Yes. The built-in 24V lithium battery supports more than 8 hours of continuous operation, making it suitable for outdoor and on-site testing.

Why Work With KSTONE
  • Professional SF6 gas equipment manufacturer
  • Extensive GIS industry application experience
  • OEM & customized solution support
  • Fast technical response
  • Stable industrial-grade equipment
  • Global B2B export experience
Request a Quote for Dew Point Analyzer

Send us your technical requirements and application details.

Our engineering team will provide a suitable Dew Point Analyzer within 24 hours.

Email: info@kstone-sf6.com